Enhancing Frequency Event Detection in Power Systems Using Two Optimization Methods with Variable Weighted Metrics
Guardat en:
| Publicat a: | Energies vol. 18, no. 7 (2025), p. 1659 |
|---|---|
| Autor principal: | |
| Altres autors: | , , |
| Publicat: |
MDPI AG
|
| Matèries: | |
| Accés en línia: | Citation/Abstract Full Text + Graphics Full Text - PDF |
| Etiquetes: |
Sense etiquetes, Sigues el primer a etiquetar aquest registre!
|
| Resum: | This research presents a novel technique that refines the performance of a frequency event detection algorithm with four adjustable parameters based on signal processing and statistical methods. The algorithm parameters were optimized using two well-established optimization techniques: Grey Wolf Optimization and Particle Swarm Optimization. Unlike conventional approaches that apply equally weighted metrics within the objective function, this work implements variable weighted metrics that prioritize specificity, thereby strengthening detection accuracy by minimizing false-positive events. Realistic small- and large-scale frequency datasets were processed and analyzed, incorporating various events, quasi-events, and non-events obtained from a phasor measurement unit in the Western Interconnection. An analytical comparison with an algorithm that uses equally weighted metrics was performed to assess the proposed method’s effectiveness. The results demonstrate that the application of variable weighted metrics enables the detection algorithm to identify frequency non-events, thereby significantly reducing false positives reliably. |
|---|---|
| ISSN: | 1996-1073 |
| DOI: | 10.3390/en18071659 |
| Font: | Publicly Available Content Database |